Free Electrical calculator

Transformer current calculator

Calculate primary and secondary full-load current from transformer kVA rating and winding voltages.

Enter the project values

All values remain in your browser. Review the assumptions before using the result.

Your result will appear here.Calculate to see the outputs, formula and substituted working.

How the calculation works

Full-load current on both sides from the nameplate kVA rating.

Formula

I = S ÷ V (1Φ) or I = S ÷ (√3 × VLL) (3Φ)

Worked example

ArrangementThree-phase
Rating500 kVA
Primary11,000 V
Secondary400 V
Expected currents26.24 A / 721.69 A

Assumptions and limitations

Assumptions

  • The kVA rating applies to both windings.
  • Three-phase voltages are line-to-line.

What this does not check

  • Does not include losses, impedance, vector group, inrush, harmonics or tap position.
  • Does not size protection, conductors or switchgear.
Formula version: 1.0 · Last reviewed: 16 August 2026

Related calculators

Engineering basis: first-principles electrical relationships using user-entered values. The page does not reproduce BS 7671 tables or establish compliance. Complete the project-specific design against the current BS 7671 information, manufacturer data and the applicable project requirements.
Your feedback

Help improve this calculator.

Spotted a formula issue, missing unit or useful output? Tell us what you would change.

Optional support

Help keep MEP Visit free.

MEP Visit calculators, templates and guidance are free to use. If a resource has saved you time, you can make an optional one-off support payment towards developing more free MEP resources.

You choose the amount from £2. No subscription. Payment page provided by Stripe.