Generator current calculator

Convert a generator rating in kVA or kW to full-load line current for single-phase or balanced three-phase output.

Enter the project values

All values remain in your browser. Review the assumptions before using the result.

Use line-to-line voltage for three-phase.
Your result will appear here.Calculate to see the outputs, formula and substituted working.

How the calculation works

Nameplate rating converted to steady-state line current.

Formula

I = S ÷ (√3 × VLL) or I = P ÷ (√3 × VLL × PF)

Worked example

Basis250 kVA
ArrangementThree-phase
Voltage400 V
Expected current360.84 A

Assumptions and limitations

Assumptions

  • The generator is operating at rated steady-state output.
  • Three-phase output is balanced.

What this does not check

  • Does not assess motor starting, step loads, transient voltage dip, harmonics or derating.
  • Does not select a generator or protective devices.
Formula version: 1.0 · Last reviewed: 16 August 2026

Related calculators

Engineering basis: first-principles electrical relationships using user-entered values. The page does not reproduce BS 7671 tables or establish compliance. Complete the project-specific design against the current BS 7671 information, manufacturer data and the applicable project requirements.
Your feedback

Help improve this calculator.

Spotted a formula issue, missing unit or useful output? Tell us what you would change.

Optional support

Help keep MEP Visit free.

MEP Visit calculators, templates and guidance are free to use. If a resource has saved you time, you can make an optional one-off support payment towards developing more free MEP resources.

You choose the amount from £2. No subscription. Payment page provided by Stripe.